Table of Contents
Heat in a laundry's drain water can be assessed at different boundaries. The heat content of a selected stream does not establish how much passed through a heat exchanger or how much the process actually received. An owner needs separate measurements at those boundaries for the same period, together with the electricity consumed by the recovery system's auxiliary equipment.
The practical outcome is a simple record of three thermal boundaries, the data sources and any unknown quantities. If useful delivery has not been measured, do not replace it with the exchanger outlet total. The example below explains the calculation with fictional inputs. It does not forecast savings for a laundry or prescribe washing, water treatment or equipment maintenance conditions.
Three boundaries
The first boundary covers the drain stream included in the analysis. Its heat content is calculated against a chosen reference temperature and the measured quantity of water. This conditional quantity describes the source but does not establish that all of that heat can be technically extracted. The result depends on the stream boundary, the reference and the data available for the selected period.
The second boundary shows heat transferred to the receiving side of the heat exchanger. It concerns a specific point and period rather than the whole potential of the drain water. The third boundary shows heat actually delivered to a defined process user. If other branches or a thermal store lie between those points, the quantities may differ over the same interval.
Record separately the electricity used by equipment included in the defined recovery system. It is expressed in electrical kilowatt-hours. Thermal and electrical quantities can share the same energy unit, but they represent different flows. Do not treat them as automatically interchangeable or subtract one from the other and call the result a proven financial saving.
Define the stream
The register should identify which machines and drains are included at the measurement point and which pass outside it. Record the period, the source of the water quantity and temperature data, and the location of each measurement. If other sources enter the common stream, distinguish them using available evidence or mark the shared boundary. An unknown contribution from another process cannot simply be attributed to the laundry.
State the reference temperature used to describe the source. It is a calculation basis, not an instruction to change water temperature. A comparison between periods using different references needs an explanation. Also record whether a quantity covers the whole stream for the period or only the part with usable observations. A complete-looking daily value should not conceal missing measurements within the day.
A laundry can operate unevenly. One daily total does not show when the drain flow occurred or whether the receiving side had a demand at that time. Time series can reveal that relationship when clocks, intervals and boundaries are aligned. A gap remains a gap. Do not enter zero flow or zero heat without evidence that it was actually zero.
Measure transfer
On the receiving side of the exchanger, a heat calculation needs information about flow and temperature change within that side over matching time intervals. A responsible professional should assess the source and calculation method for the actual fluid and instruments. If only temperature is known, a temperature difference by itself does not give an amount of transferred energy.
Identify shared meters as well. If one instrument covers several users, do not assign its entire total to one process without a supported allocation. If one meter's value is already included in another total, adding it again creates double counting. Keep the boundary diagram with the table and date for which it represents the actual system.
Transferred heat need not equal the heat received by the process over the same interval. The difference can include a change in stored heat, losses or flows outside the measurement. If there is not enough information to distinguish them, show the difference as unallocated. It does not automatically become a loss and it does not prove an equipment fault.
Useful delivery
Define the particular process boundary at which the team wants to see useful delivery. Record which users are included in that reading, whether other heat sources lie between exchanger and process, and whether their contributions can be separated. If a process inlet receives heat from several sources and only their combined flow is known, the recovered share remains unknown without further evidence.
Compare transferred and actually delivered heat for the same period. Where a system has thermal storage, its opening and closing states may differ. A short-window result cannot be treated as a complete balance without that information. Even over a longer period, unmetered branches and measurement uncertainty remain separate questions for the site team.
Worked example
Imagine one measured stream boundary over one period. The example assumes 1,000 kg of water, a mass-weighted average temperature of 40 °C and a reference temperature of 20 °C. Assume a constant specific heat capacity of 4.18 kJ per kg per degree. These are fictional inputs for arithmetic, not recommended temperatures or process requirements.
| Quantity for the period | Illustrative result | Meaning |
|---|---|---|
| Selected stream heat content above the reference | 23.2 kWh | Source description, not guaranteed extraction |
| Transferred to receiving side | 12 kWh thermal | Separate fictional exchanger-boundary measurement |
| Delivered to defined process | 9 kWh thermal | Separate fictional process-boundary measurement |
| Auxiliary system electricity | 1.5 kWh electric | Separate reading, not subtracted as a cost |
Heat content is 1,000 × 4.18 × (40 - 20) = 83,600 kJ. Divide by 3,600 to obtain approximately 23.2 kWh. The table's 12 and 9 values are independent fictional measurements, not values inferred from a universal recovery percentage. For the same defined boundary and period, their difference is 3 kWh.
For simpler arithmetic only, the example assumes no other heat source between the two points and no meter error. The 3 kWh is a combined unallocated remainder that may include a change in storage, losses or unmeasured outputs. Its components are unknown without separate evidence. The 1.5 kWh electric is recorded alongside the thermal data, but is not included in the thermal remainder.
Compare periods
To assess actual operation, compare periods with known boundaries and sufficient data. Record the amount of laundry processed or another activity measure if available and matched to the same time. Different workloads can change the total flows. Without that context a lower figure does not establish better or worse system performance.
Mark changes to the scheme, heat sources and measurement points. Keep original files, units, interval lengths and the calculation version. If an instrument records a cumulative value, compare the difference between its readings with the interval sum for the same period. Leave an unexplained discrepancy open and mark the outcome as preliminary. Do not fill a missing section with an assumed average without identifying it as an estimate and evaluating its suitability.
When presenting results, show coverage beside each total. For example, a heat quantity from a receiving-side meter may cover a different set of hours from a process-side reading. Those two totals are not a valid balance until their shared interval and exclusions are clear. Keep any unmatched readings as separate evidence rather than discarding them merely to make the figures agree.
Account for electricity
List the electrical loads included in the auxiliary boundary and the period of each reading. Where an electrical meter also supplies unrelated equipment, identify the shared scope. Do not label the whole reading as recovery-system electricity unless the allocation is supported. A system may have several auxiliary components, but the article does not assume that every laundry uses the same equipment.
Electricity consumption describes an additional input to the defined system. It does not by itself identify the source of that electricity, establish a reduction in another fuel, or prove a net financial benefit. Those questions require their own site data and assessment. Keeping the electrical record separate makes the thermal balance easier to interpret and prevents a simple energy subtraction from being presented as a bill calculation.
Give specialists the record
Provide a diagram of the three boundaries, known sources and users, drain observations, transferred heat, process delivery and separate electrical use. Include missing records and the decision needed from the assessment. Site specialists determine the measurement scope, whether the data are suitable and how the analysis applies to the actual system.
For the wider electrical profile of a business, see the guide to sizing solar from an electricity load profile. Discuss the electrical data boundary with ONG Solar. Decisions about the thermal system and process conditions remain with the laundry's responsible professionals.