To assess the electrical load of an industrial electric steam generator for a solar PV project, start with one completed production operation and match its log to the electricity meter. Record the steam supplied and the condensate returned in separate columns using the readings from their respective meters. The solar assessment uses the time series of electrical energy in kWh. The steam and condensate records explain what was happening in the process while the electrical load was present.
Choose a completed operation
Start with a production record that identifies the work unambiguously. It may give a batch number or work order, a line or area name, a date and the recorded outcome. Match the start and finish times to the shift log. If the export contains several events with similar names, ask the record owner to confirm which event represents the operation you want to assess.
A finished batch and the end of its electrical load can have different timestamps. Look at the adjacent meter intervals alongside the shift entries. Separate the preparation period, steam supply and any recorded load after steam supply has ended. If a second operation has already begun at the end of the window, distinguish its record where possible. Otherwise flag the overlap and keep the readings at the level supported by the files.
One completed run shows the load for a particular production task. Add a short note about the shift to help someone judge whether the run can be compared with others. Record whether the work started after an extended pause, whether it followed another operation and whether another steam user was active at the same time. Use the shift evidence and keep any unresolved context open for the production team to confirm.
Identify the electricity metering point
Record where the electrical series was measured. If it comes from the dedicated generator feeder, match the meter label to the equipment records. If the meter covers an entire panel, the data may include other electrical loads. Keep that series at panel level. A separate total for the generator needs confirmed disaggregated records or a dedicated measurement series.
Check what each column in the export represents. For a cumulative electricity register, the difference between two kWh readings gives the energy used over that interval. If the export already contains interval kWh, add values for non-overlapping periods. Flag gaps, meter resets and duplicate rows before making the total. Leave an interval of unknown consumption blank and report the length of the gap with the result.
If a meter interval straddles the boundary between two stages, check whether finer source intervals are available. Where you only have a single total, keep it for the full interval and note both events. Allocating energy by the minute would assume constant power across the entire interval. Keep the original measurement boundary if the export does not support that assumption.
The nameplate and the meter export can use different units. Electrical power in kW and steam output per hour describe different quantities. For a completed operation, record the observed kWh from the named electrical feeder. Power and elapsed time can be used to calculate energy when the power value is a known average for that entire interval. If the power field means something else, confirm how it was derived before using it.
Read steam supply and condensate return separately
Mark the metering point for the steam supply record. A meter at the generator outlet covers the steam that crossed that point. If the line splits farther downstream to serve several users, the outlet total cannot establish the mass delivered to one user. Record whether each export field is interval mass, a cumulative mass reading or a flow-rate value at a particular timestamp.
Read the returned condensate from its own metering point. If the meter is on a common return, note which areas are connected based on the supplied process diagram. If the log cannot tie a return to an individual batch, keep the recorded mass against the line and the observation window. Retain the measurement point and the source record so that someone else can reconstruct the boundary later.
Compare the timestamps of the two series. Return flow can appear in the log after steam supply has ended. If you have a record beyond the end of the electrical window, keep it with its own timestamp. Where condensate from a preceding or subsequent operation could be present, record it as an observation of the line without assigning it to the selected batch. Its timing helps show the lag while its origin remains open.
Keep kilograms of mass separate from electrical kWh. Subtracting mass readings from different points over an incomplete return window gives a difference between the recorded values. An estimate of makeup water or thermal energy requires measurements at the relevant boundary. A thermal estimate also needs information about the state of the measured flows and a consistent energy balance.
Worked example for one run record
All numbers below are fictional and serve to demonstrate the arithmetic. The shift log identifies one completed operation with three time rows. The electricity export gives energy per interval from a dedicated feeder. Steam mass is recorded at the outlet and condensate mass comes from a common return line. The clocks have been reconciled. The return record contains no batch identifier.
| Interval | Shift log entry | Feeder, kWh | Steam, kg | Return line, kg |
|---|---|---|---|---|
| 08:30-09:00 | Preparation | 12 | 0 | 0 |
| 09:00-10:00 | Steam supply | 56 | 60 | 10 |
| 10:00-10:30 | Operation completed with a later return record | 7 | 0 | 24 |
The three non-overlapping electricity intervals total 12 + 56 + 7 = 75 kWh on the feeder. Over the same window, the steam meter records 60 kg and the separate return line meter records 10 + 24 = 34 kg. A zero in the table means the meter reported zero for that interval. An absent reading would need a missing-data label.
The records show return flow during the observation period after steam supply ended. You can describe 60 − 34 = 26 kg as an arithmetic difference between readings within the selected window. The records do not establish the origin of the returned mass, so the difference does not quantify losses or makeup water. For solar assessment, keep the time intervals and the 75 kWh measured on the named feeder.
Decide which conclusions should stay open
A shift total can establish the consumption recorded at its measurement point. A comparison with PV generation also needs the intervals when that energy was used. For example, if the log only confirms that preparation ended before steam supply began, the allocation of kWh between those events remains unknown. Keep the shift total and its time window. Mark the question that a more detailed electrical series would need to answer.
If return readings are absent, the electrical assessment can still be completed when its own records are sufficient. Use the condensate column to identify the missing file or measurement. If condensate return was measured but steam supply is only noted as an event, label the measured return mass and the occurrence of steam supply separately. This lets the engineer distinguish a measurement from an observation and see which question remains open.
Compare the electricity series with solar generation
Check the calendar date, time zone and interval timestamp convention before aligning the feeder series with solar generation. One export may identify intervals by the start time and another by the end. A label of 09:00 can refer to different time windows in those files. Use a common resolution supported by the source data. Our guide to solar interval data explains how the choice of interval changes the visibility of short events.
Bring in the whole-site electrical load at the relevant metering point and mark whether it already includes the steam generator. If it does, use the feeder trace to explain that portion of the site load. Adding the feeder kWh again would overstate demand. Label generation from an existing installation separately from a modeled series for a proposed PV system so a reviewer knows the origin of the figures.
Time overlap helps identify intervals for closer assessment. Other loads can share the same bus, so comparing the two series does not show how much solar generation went to the steam generator specifically. Sizing commercial solar with a load profile requires broader site records. Give the analyst the annotated run as one part of that profile and flag any overlap with other production operations.
What to hand over for a site assessment
Package the original exports and a short explanation alongside the totals. Give the operation ID, the start and end times, the units and the method used to obtain each reading. For all three series, identify the meter, the feeder or pipe and any known branches. List gaps, combined flows and late entries separately. Point to the file and row that a second person can use to check each reported total.
For example, the equipment list may name a meter after the steam generator while the panel drawing places the same identifier on a shared feeder. Keep both documents with their dates, flag the discrepancy and leave the consumption at feeder level until its scope is confirmed. Apply the same approach when two records describe a return line as dedicated and shared.
Before comparing two runs, check that completion has the same meaning in both logs, that the metering coverage matches and that the work itself is comparable. If one run has dedicated electricity data and the other only a panel total, record that difference. The record owner can confirm the measurement scope and the analyst can decide whether the evidence is adequate for comparison with the solar profile.
Even one well-documented operation can go into a solar site audit alongside the wider facility profile. For a fuller assessment, gather repeat observations across shifts and mark days when the production task changed. Run frequency, site operations and available metering vary by facility. Apply the findings to the production area and time period represented in the records.