Compare two completed refrigeration cycles through the same observed baseline and assess coincident solar energy.

ReadAll Articles
Cold room, solar panel and a chart with two lines

Table of Contents

A refrigeration system can use electricity both during defrost and after the principal defrost phase has ended. Looking only at the signal that defrost has finished leaves some subsequent consumption outside the comparison. At a site with solar generation, the team also needs to see when that consumption coincided with electricity available from the PV system.

A useful unit of analysis is one already completed cycle from the start of defrost through the return to a defined observed baseline. Compare two such cycles using the same meter boundary and similar operating conditions. This is a review of existing records. It does not call for changing schedules, settings or storage conditions to follow solar output.

Define the cycle

Use the equipment log to identify the start and end of the defrost phase. Then include the period until the system returns to a previously described observed baseline. Electricity use can differ from normal during this period, including through shared refrigeration components. The actual components depend on the system, so establish the boundary from the site's documentation and available records.

The end of a defrost signal and the end of the complete comparison interval do not necessarily coincide. Mark both separately. In an actual log, the return can be described using operating indicators and available measurements agreed by the responsible specialists. Preserve the definition itself instead of recording only that the system has recovered.

The baseline in this analysis is a condition for comparing data. It is not a product temperature limit or a rule for safe storage. Responsible specialists determine suitable conditions and the permitted process for the actual goods and equipment. The team does not alter the system or conduct a new experiment on stock to obtain a data point.

Set the meter boundary

Identify which parts of the refrigeration system are covered by the meter. One room may use shared compressors, fans, controls or other components alongside neighbouring zones. If those loads are included in the measurement, the result applies to the entire measured boundary. It cannot automatically be attributed to one room.

Both cycles need the same boundary and measurement units. If components are metered separately, their intervals must align and shared equipment must not be counted twice. When part of the equipment is outside the measurement, name it and do not describe the sum as electricity for the complete refrigeration system.

To estimate solar coincidence, separate synchronized records are also needed for PV generation and the other site loads. Establish whether a battery, other sources or exports were present. If the available data cannot distinguish the flows, that is a limitation of the result. It is not a reason to assume that all PV generation supplied refrigeration.

Choose comparable cycles

Choose two completed cycles of the same system with known starts, defrost ends and returns to the same baseline definition. Use existing records to establish whether loading, product condition, access to the rooms and operation of other zones inside the meter boundary were similar. Preserve available information about outdoor conditions and unusual events as well.

Similar does not mean identical. A new delivery, maintenance work, a sensor outage or activity in another room can alter the load. Record these differences alongside the result. If information about product conditions or the shared load is missing, the responsible specialist needs to review whether the periods are comparable.

Use only complete valid intervals with aligned clocks. A missing reading, an unexplained spike or an undocumented meter replacement needs its own flag. Do not fill a gap with zero. If the cycle boundary falls inside an interval and no finer record exists, state the uncertainty or postpone the comparison.

A fictional example

The following invented data describe two already completed cycles A and B for the same facility. Each covers six consecutive intervals of 15 minutes. Refrigeration demand and available solar power are assumed constant within each interval. Under this assumption the model takes the lower energy total in each interval as the overlap. On a real site, quarter-hour totals alone do not establish that coincidence.

The same meter covers the whole refrigeration facility, including shared equipment. The logs for both cycles show similar product condition and comparable operating circumstances. In this example, the baseline was defined in advance as a recurring operating state confirmed by the log, with two consecutive intervals of 6 kWh each. That indication is met before the start and after the end of each cycle. It is a fictional comparison marker, not a standard or a product-quality test.

The first two intervals cover the defrost phase. The remaining four cover the period until the defined return is complete. The final two intervals confirm the baseline described above. Each cycle is indexed from its own actual event, so matching row numbers do not mean the same time of day.

Fictional data for two completed cycles, kWh per interval
IntervalCooling AAvailable ACooling BAvailable B
16084
282106
310484
48264
56464
66460
Total44164422

The available column shows modelled solar energy after simultaneous supply to other site loads and before allocation to the refrigeration boundary. In each interval, other loads receive priority and consume 4 kWh of the fictional PV generation. PV output for A is therefore 4, 6, 8, 6, 8 and 8 kWh, while output for B is 8, 10, 8, 8, 8 and 4 kWh. This example has no battery, other source or grid export.

Read the result

For each interval, take the smaller of the refrigeration facility's consumption and the solar energy available after other loads. Under the fictional priority rule for the rest of the site, every available value in the table is below the refrigeration demand. The resulting modelled coincidence is 16 kWh for A and 22 kWh for B.

Each complete period uses 44 kWh. Modelled coincidence is therefore about 36 percent for A and 50 percent for B. The difference of 6 kWh describes only these two fictional data sets and the selected allocation rule. It does not prove savings, establish the cause of the difference or imply that any cycle should be moved.

Defrost occupies the first two intervals in the example, but the entire sum represents electricity for the measured system over the full period. The 44 kWh cannot be called incremental defrost energy without a separate supported comparison against an appropriate baseline scenario. The last two intervals are included because they confirm the example's defined return.

A separate subtotal shows why the defrost end signal does not describe the whole period. In the first two intervals, the facility uses 14 kWh in A and 18 kWh in B. From that signal to the end of the defined return it uses 30 and 26 kWh respectively. The modelled solar coincidence in those two parts is 2 and 14 kWh for A, and 10 and 12 kWh for B.

These figures do not establish that every kilowatt-hour during recovery was caused by defrost. Shared compressors and other equipment may also serve normal demand or other zones. The table reports the whole measured boundary over the defined window. A claim about incremental effects would require a different question and supporting data that the fictional example does not contain.

Resolution and gaps

When generation and demand vary within an interval, the smaller of their interval totals can overstate actual coincidence. Solar energy might have been produced at the beginning while the refrigeration load occurred at the end. Finer synchronized intervals or power data provide a better basis when their quality and timestamps are confirmed.

It also matters whether the PV measurement and load are on the same side of the system and whether losses and potential energy sources are accounted for. If a battery was charging or discharging, a separate flow model is needed. Without this distinction, the available values cannot reliably assign consumption to solar generation.

The assumed priority for other loads is an accounting convention in this example. Another agreed allocation rule could produce a different share for the refrigeration facility even though physical site generation remains the same. Preserve the rule alongside the table so another analyst can reproduce the result and understand its limits.

What to share

Prepare the meter boundary diagram, two time series, event log and baseline definition. Add product-condition information, shared zones, other loads and missing data. Ask the refrigeration specialist whether the periods are comparable and the return is correctly defined. Ask the energy specialist to review the meter boundaries and simultaneous flows.